Cables LAN Cabling About WW Contact Home

 

 

Chapter 7.2.1

Single Pair & Single Triad PVC Insulated and Jacketed Foil Shielded 300V Instrument Cables + Moisture Barrier

Physical Description

Power-Limited Tray Cables conforming to UL Subject 13 and NEC Article 725 Class 2 Circuits.
The cables can be used for instrument interconnections in process plant for LF control applications.
Each cable contains one twisted pair or one twisted triad.
The cables are overall foil-shielded and jacketed with FR-PVC compound.
200 aluminum foil, bonded to itself and to the outer heavy-duty, black, UV resistant PE outer jacket provide a vapor-tight moisture-barrier.

Conductors

Stranded bare annealed copper, Class B ASTM B-8.

Insulation type Flame retardant PVC compound, conforming to BS 6746 Type 5.
Insulation thickness 0.4 mm nom.

Color code

Pair: Black x White.   Triad: Black x White x Red.

Conductor arrangement

The conductors are twisted together with a 50mm max. lay length.

Core warp

Polyester tape, providing 100% coverage.

Drain wire

Stranded annealed tinned copper.

Overall shield

Polyester-aluminum tape, foil face in, providing 100% coverage.

Inner Jacket

Heavy-duty Flame-retardant PVC compound, UV resistant, conforming to BS 6746 Type 9.

Rip-cord PA stranded rip-cord (14 Kgf) laid under the jacket for easy jacket removal.
Inner Jacket thickness 0.5 mm nom.
Color Black, RAL 9005.
Rip-cord PA stranded rip-cord (14 Kgf) laid under the MB for easy jacket and MB removal.

Moisture barrier

200 bonded aluminum tape, copolymer coated (both sides).

Outer Jacket

Heavy-duty Flame-retardant PE compound, UV resistant.

Color Black, RAL 9005.
Surface printing WW P/N, Cable description, Batch Number, Sequential meter-mark.

Physical Properties

Minimum Bend Radius

10 x D

Storage Temperature

-20 to +60C

Operating temperature

-20 to +90C

Flame test

IEC 60332-1

Electrical Properties @ 20C

Continuous working voltage

300 V rms max.

Insulation Dielectric strength

2000 V rms min/ 1 minute (between conductors)

Jacket Dielectric strength

5000 V rms min/ 1 minute (shield to water)

Velocity of propagation

55% nom. @ 1 KHz

WW P/N Construction Conductor Insulation OD Inner Jack. Thickness Inner OD Outer Jack. Thickness Cable OD Drain Wire Total Weight DC Resistance
      mm mm mm mm mm   Kg/Km Ohm/Km
DZ502G10 1x2x20 AWG 7x0.32mm 1.75 0.5 4.6 0.8 7.5 22 AWG 80 35.9
DZ503G10 1x3x20 AWG 7x0.32mm 1.75 0.5 4.8 0.8 8.0 22 AWG 90 35.9
DZ502H10 1x2x18 AWG 7x0.40mm 2.00 0.5 5.0 0.8 8.0 20 AWG 75 22.0
DZ503H10 1x3x18 AWG 7x0.40mm 2.00 0.5 5.4 0.8 8.5 20 AWG 90 22.0
DZ502J10 1x2x16 AWG 7x0.49mm 2.35 0.5 5.7 0.8 8.7 20 AWG 90 13.9
DZ503J10 1x3x16 AWG 7x0.49mm 2.35 0.5 6.0 0.8 9.0 20 AWG 115 13.9
DZ502K10 1x2x14 AWG 7x0.61mm 2.85 0.5 7.6 0.9 11.0 16 AWG 140 10.0
DZ503K10 1x3x14 AWG 7x0.61mm 2.85 0.5 7.9 0.9 11.5 16 AWG 185 10.0

 